INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

WARNING: For propane/LP

units, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under Installing

Gas Piping to Fireplace Loca-

tion, page 13.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

fireplace gas regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 17).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

or propane/LP supply to equipment shutoff

valve for propane/LP gas (see Figures 18 or

19). Apply noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Figure 18 - Checking Gas Joints for

Natural Gas Fireplace

Figure 17 - Equipment Shutoff Valve

Manual Gas Valve

Gas Meter

Equipment
Shutoff Valve

Figure 19 - Checking Gas Joints for

Propane/LP Gas Fireplace

Propane/LP
Supply Tank

Manual Gas Valve

Equipment
Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve