Troubleshooting – Desa VTGF33NRB User Manual

Page 29

Advertising
background image

www.desatech.com

113134-01F

9

OBSERVED PROBLEM

When ignitor button is pressed,

there is spark at ODS/pilot but no

ignition (manual ignition mode)

ODS/pilot lights but flame goes

out when control knob is released

(manual ignition mode)

REMEDY

1. Turn on gas supply or open

equipment shutoff valve

2. Turn control knob to PILOT

position full counterclockwise

3. Continue holding control knob

in full counterclockwise posi-

tion. Repeat igniting operation

until air is removed

4. Contact local propane/LP gas

company

5. Clean ODS/pilot (see Clean-

ing and Maintenance, page

25) or replace ODS/pilot as-

sembly

6. Replace gas regulator

1. Turn control knob fully coun-

terclockwise

2. After ODS/pilot lights, hold

control knob for 30 seconds

3. Fully open equipment shutoff

valve

4. A) Contact local natural or

propane/LP gas company

B) Clean ODS/pilot (see

Cleaning and Maintenance,

page 25) or replace ODS/pilot

assembly

5. Hand tighten until snug, then

tighten 1/4 turn more

6. Replace pilot assembly

7. Replace control valve

TROUBLEShOOTING

Continued

POSSIBLE CAUSE

1. Gas supply turned off or

equipment shutoff valve

closed

2. Control knob not in PILOT

position

3. Air in gas lines when in-

stalled

4. Depleted gas supply (pro-

pane/LP only)

5. ODS/pilot is clogged

6. Gas regulator setting is not

correct

1. Control knob not fully turned

counterclockwise

2. Control knob not held long

enough

3. Equipment shutoff valve not

fully open

4. Pilot flame not touching

thermocouple, which allows

thermocouple to cool, caus-

ing pilot flame to go out. This

problem could be caused by

one or both of the following:

A) Low gas pressure

B) Dirty or partially clogged

OD S/pilot

5. Thermocouple connection

loose at control valve

6. Thermocouple damaged

7. Control valve damaged