Installation – Desa VRL30PR User Manual

Page 10

Advertising
background image

www.desatech.com

110021-01M

10

LOG SIZING REQUIREMENTS

Minimum Firebox Size

Log

Front

Rear

Size Height Depth Width Width*
24"

17"

14"

28"

20

1

/

4

"

30"

17"

14"

34"

22

3

/

8

"

*Measured at 14" Depth

Figure 4 - Minimum Clearance for

Combustible to Wall

*Minimum 16 inches from Side Wall

*

Example

NOTICE: Manual control heaters

may be used as a vented product.

If so, you must always run heater

with chimney flue damper open.

If running heater with damper

open, noncombustible material

above fireplace opening is not

needed. Go to Installing Damper

Clamp Accessory for Vented

Operation, page 13.

Minimum Noncombustible Material
Clearances

If Not Using Mantel

Note:

If using a mantel, proceed to If Using

Mantel below. If not using a mantel, follow the

information below.
You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncom-

bustible material must extend at least 8" up. If

noncombustible material is less than 12", you must

install the fireplace hood accessory. See Figure 5,

page 11, for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 13.

If Using Mantel

You must have noncombustible material(s) above

the fireplace opening. Noncombustible materials

(such as slate, marble, tile, etc.) must be at least

1/2 inch thick. With sheet metal, you must have

noncombustible material behind it. Noncombustible

material must extend at least 8 inches up (for all

models). If noncombustible material is less than

12", you must install the fireplace hood accessory

(24" model only). Even if noncombustible material

is more than 12", you may need the hood accessory

to deflect heat away from your mantel shelf. See

Figures 5 and 6, page 11 and Figure 7 page 12,

for minimum clearances.
IMPORTANT:

If you cannot meet these minimum

clearances, you must operate heater with chimney

flue damper open. Go to Installing Damper Clamp

Accessory for Vented Operation, page 13.

INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)

WARNING: Maintain the

minimum clearances. If you can,

provide greater clearances from

floor, ceiling and adjoining wall.

INSTALLATION

Continued

Carefully follow the instructions below. This will

ensure safe installation into a masonry, UL127-

listed manufactured fireplace or certified vent-free

firebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace

cabinet to any combustible material and wall

should follow diagram in Figure 4.

Example:

The face of a mantel, bookshelf,

etc. is made of combustible material and

protrudes 3

1

/

2

" from the wall. This combus-

tible material must be 4" from the side of the

fireplace cabinet (see Figure 4).

Note:

When installing your gas logs into

a manufactured firebox, follow firebox

manufacturerʼs instructions for minimum

clearances to combustible materials.

B. Clearances from the top of the fireplace

opening to the ceiling should not be less

than 42 inches.

Advertising
This manual is related to the following products: