Installation – Desa VRL30PR User Manual

Page 11

Advertising
background image

www.desatech.com

110021-01M

11

Noncombustible

Requirements for

Material Distance (A) Safe Installation
12" or more

Noncombustible material okay.

Between 8"

Install fireplace hood and 12"

accessory (GA6050, GA6052 or

GA6053, see Accessories, page 41).

Less than 8"

Noncombustible material must be

extended to at least 8". See

Between 8" and 12", above. If you

cannot extend material, you must

operate heater with flue damper open.

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material

clearances, you must also meet required clearances

between fireplace opening and mantel shelf. If

you do not meet the clearances listed below, you

will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel

shelf and top of fireplace opening, a hood is not

required (see Figure 6).

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Figure 6 - Minimum Mantel Clearances Without Using Hood

Minimum Non-
Combustible
Material

Minimum Non-
Combustible
Material Height

Distances to
Underside of
Mantel

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

12"

(A)

18"

20"

22"

24"

All minimum
distances are
in inches

Log Set
All Models

2

1/2

"

6"

8"

10"