Determining Minimum Mantel Clearance
when Using a Hood
If minimum clearances in Figure 6 (page 11) are

not met, you must have a hood. When using a hood

there are still certain minimum mantel clearances

required. Follow minimum clearances shown in

Figure 7 when using a hood.

NOTICE: Surface temperatures

of adjacent walls and mantels be-

come hot during operation. Walls

and mantels above the firebox

may become hot to the touch.

If installed properly, these tem-

peratures meet the requirement

of the national product standard.

Follow all minimum clearances

shown in this manual.

NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• operate the logs only with the

flue damper open

• raise the mantel to an accept-

able height

• remove the mantel

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

Hearth

5"

Min.

Combustible

Material

14"

Min.

Combustible

Material

Noncombustible Material

Figure 8 - Minimum Fireplace Clearances

If Installed at Floor Level

Figure 9 - Minimum Fireplace Clearances

Above Combustible Flooring

Figure 7 - Minimum Mantel Clearances When Using Hood