Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 16).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas

or using compressed air.

3. Check all joints from gas meter for natural gas

or propane/LP supply to equipment shutoff

valve (see Figure 17 or 18). Apply a com-

mercial leak detection solution to all joints.

Bubbles forming show a leak.

4. Correct all leaks at once.
Pressure Testing Heater Gas
Connections
1. Open equipment shutoff valve (see Figure 16).
2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Make sure control knob of heater is in the

OFF position.

4. Check all joints from equipment shutoff

valve to thermostat gas valve (Thermostat-

Controlled Models) or control valve (Remote-

Ready Models) (see Figure 17 or 18). Apply a

noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light heater (see Operating Heater, page 20).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to Ap-

pliance, page 21 [thermostatically-controlled

models] or page 24 [remote-ready models]).

Figure 16 - Equipment Shutoff Valve

Equipment
Shutoff Valve

Propane/LP
Supply
Tank

Thermostat Gas
Valve or Control
Valve Location

Figure 18 - Checking Gas Joints

(Natural Gas Only)

Gas Meter

Equipment
Shutoff Valve

Figure 17 - Checking Gas Joints

(Propane/LP Gas Only)

Open

Closed

Equipment
Shutoff Valve

INSTALLATION

Continued

Thermostat Gas
Valve or Control
Valve Location