To enter or modify the kilowatts per pulse value, press the
key repeatedly, increasing the value of the flashing digit.
When the on-screen value is that desired, press the
key to
go to the next digit to modify the other values.
If you press the
key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
Example: To program 500 Wh per pulse: 000.500
To program 1.5 kWh per pulse: 001.500
Once the desired option has been programmed, press the
key to validate the information
and thereby finish programming the unit.
Maximum programming value: 999999 KWh.
Minimum programming value: 000.001 KWh.
Programming by alarm condition
On this screen the parameter code for which you want an alarm
to be generated is selected, based on
The
key jumps between the different options.
Table 12: Parameter codes for alarm programming�
Parameter
Code
Parameter
Code
Active power III
16
Line voltage III
45
III Inductive Power
17
Apparent power III
34
III Capacitive Power
18
Maximum Demand
35
Three-phase Cosine φ
19
Current III
36
Power factor III
20
Phase voltage III
44
Frequency
21
Once an alarm code has been selected and validated with the
key you must enter the
maximum value of the alarm condition.