-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 18


5.3.- Voltage Transformer Secondary

We can now set the value of the secondary of the voltage transformer. Only three
digits are available:

SET U
S
- - -


Same process as in point 5.2:

- "max" key: Allows us modifying the value of the blinking digit. Each time it is
pressed the value is increased.

- "min" key: Allows us the validation of the blinking digit and going to the next one.

- Press "display" to pass to the next setup option.

If the CVM-BD-420-.. is directly connected to the mains (without voltage
transformer) the values of primary and secondary must be the same, for instance
000001/001.

5.4.- Current Transformer Primary

"SET A P" and five digits appear on screen allowing us to set the primary of the
current transformer. The current green LEDs light on to avoid mistakes.

SET A
P - -
- - -