Supply voltage – CIRCUTOR CVM-BD Series User Manual

Page 8

Advertising
background image

-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 7


3.1.- INSTALLATION

Before applying AC power to the, check following points :

a.-

Supply voltage :

- Power supply V a.c. ( Single phase ) 50 ...60 Hz

230 V a.c.

- Frequency : 50 ... 60 Hz
- Supply tolerance : + 10 % / --15 %
- Connection terminals : Terminals 1 - 28
- Instrument burden : 6 VA

b.- Maximum voltage at the voltage measuring circuit:

Standard : 500 V a.c. phase-neutral / 866 V a.c. between phases

A special model CVM-BD-420-4 & CVM-BD-420-8 for 110 V measurement is

also available:

100 V a.c. phase-neutral / 173 V a.c. between phases

c.- Maximum admissible current : Transformer of In / 5 A a.c.

d.- Operation conditions :

- Operating temperature : 0 to 50ºC
- Humidity : 25 to 80 % R.H. non-condensing

e.- Safety : Designed to meet protection class II as per EN 61010.