CIRCUTOR computer SMART III-Fast Series User Manual

Page 41

Advertising
background image

Active alarms

Parameters

Active alarm code E01 to E017

(

Table 9

)

If there are more than 4 alarms, the

informationisscrolledonthescreen�

Table 9: Alarm codes�

Code

Description

E01

No current�Theloadcurrentislowerthantheminimumvalueorsomeofthe

currenttransformers(CT)arenotconnected�

Itisactivatedwhenthesecondarycurrentofthetransformerislowerthan50

mAinsomeofthephases�

Theunitdisconnectsthecapacitorsautomatically�

E02

Overcompensation�Theunitmeasurescapacitivepowerbutallthestages

aredisconnected�

ThiscanbeduetoanincorrectadjustmentoftheC/Kparameter�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof90

seconds�

E03

Undercompensation�Theunitmeasuresinductivepowerbutallthestages

aredisconnected�

ThiscanbeduetoanincorrectadjustmentoftheC/Kparameter�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof90

seconds�

E04

Overcurrent�Themeasuredcurrentexceedsthenominalcurrentby+20%

insomeofthephases�ThenominalcurrentisconsideredtobethatoftheCT

primary�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof5

seconds�

E05

Overvoltage�Thevoltagemeasuredinsomeofthephasesexceedsthecon-

figuredvoltage(Vp-n)�

Theunitdisconnectsthecapacitorsautomatically�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof5

seconds�

E06

Low voltage�Thevoltageinsomeofthephasesislowerthantheconfigured

voltage(Vp-n)�

Theunitdisconnectsthecapacitorsautomatically�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof5

seconds�

E07

Cos φ alarm�Thethree-phasecos φ islowerthanthelimitconfiguredinthe

Cosφalarm�Also,themeasuredcurrentsshouldbehigherthantheconfigured

threshold�

Inordertoavoidpossiblefalseactions,thisalarmhasapredefineddelayof15

seconds�

41

Instruction Manual

Computer SMART III FAST

Advertising