CIRCUTOR computer SMART III-Fast Series User Manual

Page 66

Advertising
background image

Table 24:Modbus memory map: programming variables (Table 10)

C/K factor

Configuration variable

Address

Valid data margin

Default value

C/Kfactor

1138

0-100(Valuex100)

100

Table 25:Modbus memory map: programming variables (Table 11)

Program

Configuration variable

Address

Valid data margin

Default value

Program

1139

1111-1999

1111

Operationtype

113A

0(FCP),1(Total),2(Sim)

0

Table 26:Modbus memory map: programming variables (Table 12)

No� of stages

Configuration variable

Address

Valid data margin

Default value

No�ofstages

113B

0-6(ComputerSMARTIIIFAST6)

0-12(ComputerSMARTIIIFAST12)

6

12

Table 27:Modbus memory map: programming variables (Table 13)

Connection and reconnection time

Configuration variable

Address

Valid data margin

Default value

Connectiontime

113C

0-999networkcycles

10

Reconnectiontime

113D

0-999networkcycles

50

Table 28:Modbus memory map: programming variables (Table 14)

Alarm: Voltage THD

Configuration variable

Address

Valid data margin

Default value

LowValue

1140

0-100%

5

HiValue

1141

0-100%

10

Table 29:Modbus memory map: programming variables (Table 15)

Alarm: Current x I THD

Configuration variable

Address

Valid data margin

Default value

LowValue

1142

0-100%

4

HiValue

1143

0-100%

5

Table 30:Modbus memory map: programming variables (Table 16)

Alarm: Temperature

Configuration variable

Address

Valid data margin

Default value

LowValue

1144

0-80ºC

55

HiValue

1145

0-80ºC

70

Table 31:Modbus memory map: programming variables (Table 17)

Alarm: Leakage Current

Configuration variable

Address

Valid data margin

Default value

Searchfortheresponsiblestage

1146

0(OFF),1(ON)

0

Value

1147

10-1000mA

300

Stagesenabled

1148

0(No),1(Yes)

0

Table 32:Modbus memory map: programming variables (Table 18)

Alarm: Cos φ

Configuration variable

Address

Valid data margin

Default value

ValueofCosφ

1149

80-100(Valuex100)

95

Currentvalue

114A

0-9999A

20

TypeofCosφ

114B

0(Capacitive),1(Inductive)

1

66

Computer SMART III FAST

Instruction Manual

Advertising
This manual is related to the following products: