Cos φ alarm, 5�21�- cos – CIRCUTOR computer SMART III-Fast Series User Manual

Page 95

Advertising
background image

5�21�-COS

φ

ALARM

Inthispointthelimitforactionofthecosφalarm

canbeconfigured�

Itisactivatedeverytimethevalueofthecos

φ

dropsbelowtheconfiguredvalueandthecurrent

ishigherthanprogrammed�

Thealarmmustbeenabled(

5�19�- ENABLING

ALARMS

Pressthe

keytoentereditingmode�Itis

identifiedbythe

symbolandtheblinkingof

thedigitstobemodified�

Inordertoavoidpossiblefalseactivationsofsaidalarms,theyhaveapredefineddelayof15

seconds�

Theparameterstobeconfiguredare:



The

current value�

The

cos

φ value

andwhetheritisinductive

L

orcapacitive

C

The

keyincreasesthedigitvalueorshowsthenextoption�

The

keydecreasesthedigitvalueorshowsthenextoption�

The

keyskipstothepreviousdigit�

The

keyskipstothenextdigit�

Press

tovalidatethedata;the

symboldisappearsfromthedisplay�

Current:

Maximum value: 9999A

Minimum value: 0A

cos

φ

:

Maximum value: 1�00

Minimum value: 0�80

Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,

thebacklightofthedisplayflashesandthevalueenteredisreplacedwiththeminimumor

maximumvalue,orwiththelastvaluevalidated�

Pressthe

keytoaccessthenextprogrammingstep�

Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,

5�27�-

SIMULATION SCREEN”

95

Instruction Manual

Computer SMART III FAST

Advertising
This manual is related to the following products: