5�20�-VOLTAGEALARMS

Inthispointthephase-phasevoltagethresholds
abovewhichtheovervoltagealarm(

E05

)andthe

novoltagealarm(

E06

)shouldbetriggeredcanbe

configured�

Thealarmmustbeenabled(

5�19�- ENABLING

ALARMS”

Pressthe

keytoentereditingmode�Itis

identifiedbythe

symbolandtheblinkingof

thedigitstobemodified�

Inordertoavoidpossiblefalseactivationsofsaidalarms,theyhaveapredefineddelayof5

seconds�

Theparameterstobeconfiguredare:


The

value of the overvoltage alarm:

HI

The

value of the no voltage alarm:

LO

Whenanyofthetwoalarmsaretriggered,theunitentersthe

Disconnectionstatusand

disconnectsallthestages�Theunitdoesnotreturntoitsnormaloperatingstatusuntilthe

causeforthealarmdisappears�

The

keyincreasesthedigitvalue�

The

keydecreasesthedigitvalue�

The

keyskipstothepreviousdigit�

The

keyskipstothenextdigit�

Press

tovalidatethedata;the

symboldisappearsfromthedisplay�

Overvoltage alarm:

Maximum

value:

99999V

Minimum

value:

0V

No voltage alarm:

Maximum

value:

99999V

Minimum

value:

0V

Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,

thebacklightofthedisplayflashesandthevalueenteredisreplacedwiththeminimumor

maximumvalue,orwiththelastvaluevalidated�

Pressthe

keytoaccessthenextprogrammingstep�

Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,