Current x i thd alarm – CIRCUTOR computer SMART III-Fast Series User Manual

Page 97

Advertising
background image

Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,

thebacklightofthedisplayflashesandthevalueenteredisreplacedwiththeminimumor

maximumvalue,orwiththelastvaluevalidated�

Pressthe

keytoaccessthenextprogrammingstep�

Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,

5�27�-

SIMULATION SCREEN

5�23�-CURRENTxITHDALARM

Inthispointthethresholdsabovewhichthealarm

forthepercentageofthevalueofthecurrentx
ITHD(

E09

)isactivatedcanbeconfigured�

Thealarmmustbeenabled(

5�19�- ENABLING

ALARMS

The programmed values are useful for the 3

phaseswhichtheunitmeasures�

Pressthe

keytoentereditingmode�Itis

identifiedbythe

symbolandtheblinkingof

thedigitstobemodified�

Thevaluetobeprogrammedinthisalarmcorrespondsdirectlytothevalueofthetotal
harmoniccurrenttobeconsideredasthesetpoint�

For example: If you want to program a

Lo

setpoint value when exceeding a harmonic current of 200 A measured by the regulator, program

00200

directly in this section.

Theparameterstobeconfiguredare:

The

Lo

value: whentheunitexceedsthisvaluefor30minutes,alarm

E09

is

triggered,andifalarm

E11

is enabled

,

the

SMART III FASTunitentersNo Connection

statusandactivates

alarm

E11

The

HI

value: iftheunitexceedsthisvaluefor30seconds,alarm

E09

istriggered,

andifalarm

E12

isenabled,the

SMART III FASTunitenterstheDisconnection status

andactivates

alarm

E12


Iftheunitfallsbackunderthe

Lo

valuefor10minutes,itdeactivatesthealarmsandreturns

tothenormaloperatingstatus�

Inthe

No Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot

disconnectthemiftheoperationrequiresit�

Inthe

Disconnectionstatus,itdisconnectsallthestagesanddoesnotallowthemtoconnect�

The

keyincreasesthedigitvalue�

97