Installation – Desa VTGF33NRA User Manual

Page 15

Advertising
background image

www.desatech.com

110112-01C

15

WARNING: For propane/LP

units, make sure external regula-

tor has been installed between

propane/LP supply and heater.

See guidelines under Installing

Gas Piping to Fireplace Loca-

tion, page 13.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main

gas valve (control valve) and equipment

shutoff valve from gas supply piping system.

Pressures in excess of 1/2 psig will damage

fireplace gas regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas,

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 17).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas,

or using compressed air.

3. Check all joints from gas meter for natural gas

or propane/LP supply to equipment shutoff

valve for propane/LP gas (see Figures 18 or

19). Apply noncorrosive leak detection fluid

to all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

INSTALLATION

Continued

Figure 18 - Checking Gas Joints for

Natural Gas Fireplace

Figure 19 - Checking Gas Joints for

Propane/LP Gas Fireplace

Figure 17 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

Equipment
Shutoff Valve

Manual Gas Valve

Gas Meter

Equipment
Shutoff Valve

Manual Gas Valve

Propane/LP
Supply Tank

PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 17).
2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

3. Place manual ignition switch in the OFF

position.

4. Check all joints from equipment shutoff valve

to gas valve (see Figure 18 or 19). Apply

noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace, page

21). Check all other internal joints for leaks.

7. Turn off fireplace (see To Turn Off Gas to

Appliance, page 22).