Air for combustion and ventilation – Desa VTGF33NRA User Manual

Page 7

Advertising
background image

www.desatech.com

110112-01C

7

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free heater

_______ Btu/Hr

Gas water heater*

_______ Btu/Hr

Gas furnace

_______ Btu/Hr

Vented gas heater

_______ Btu/Hr

Gas fireplace logs

_______ Btu/Hr

Other gas appliances* + _______ Btu/Hr

Total = _______ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water heater

_______ Btu/Hr

Vent-free heater + _______ Btu/Hr

Total = _______ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space

can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example:

57,600 Btu/Hr (maximum the

space can support)

73,000 Btu/Hr (actual amount

of Btu/Hr used)

The space in the above example is a confined

space because the actual Btu/Hr used is more than

the maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See Ven-

tilation Air From Outdoors.

C. Install a lower Btu/Hr heater, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support, the space is

an unconfined space. You will need no additional

fresh air ventilation.

AIR FOR COMBUSTION

AND VENTILATION

Continued

40,000
33,000
73,000

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and

one within 12" of the floor on the wall connecting

the two spaces (see options 1 and 2, Figure 3). You

can also remove door into adjoining room (see

option 3, Figure 3). Follow the National Fuel Gas

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for

Combustion and Ventilation for required size of

ventilation grills or ducts.

Figure 3 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or

ducts. You must provide two permanent openings:

one within 12" of the ceiling and one within 12"

of the floor. Connect these items directly to the

outdoors or spaces open to the outdoors. These

spaces include attics and crawl spaces. Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.

Advertising
This manual is related to the following products: