420Hz for 4 sec.
410Hz for 5 sec.
407Hz for 4 sec.
For 60Hz only:
61Hz for 0.5 sec.
60.5Hz for 0.5 sec.
After this sequence, a 5 second delay will be inserted at the nominal test frequency. The
key
(backspace) will terminate the test at any time.
LOW FREQUENCY TRANSIENT
This test will change the output frequency in the following sequence:
For 400Hz and VFREQ:
375Hz for 1 sec.
380Hz for 4 sec.
390Hz for 5 sec.
393Hz for 4 sec.
For 60Hz only:
59Hz for 0.5 sec.
59.5Hz for 0.5 sec.
After this sequence, a 5 second delay will be inserted at the nominal test frequency. The
key
(backspace) will terminate the test at any time.