i Series II / iX Series II / iM Series II
•
0V for 7sec.
•
20V for 93sec.
2. 270V system:
•
0V for 7sec.
•
240V for 93sec.
The
←
key (backspace) will terminate the test at any time.
9.8.1.8.4 Emergency Test
From the MIL704 DC MENU scroll to the EMERGENCY DC entry using the up and down cursor
keys (Figure 9-58). Press the ENTER key to start the EMERGENCY TEST.
Figure 9-58: Emergency Test
VOLTAGE
This test will change the output voltage for the selected phase in the following sequence:
1. 28V system:
•
18V for 1 minute.
•
29V for 1 minute.
•
28V for 1 minute.
2. 270V system:
•
250V for 1 minute.
•
280V for 1 minute.
•
270V for 1 minute.
The
←
key (backspace) will terminate the test at any time.