Read analogue outputs (function 3) – BECKHOFF BK7300 User Manual

Page 26

Advertising
background image

MODBUS

22

BK7300


Read Analogue Outputs (Function 3)

READ HOLDING
REGISTERS

Function 3 can be used to read the output words and the registers.

In this example the first two analogue outputs of slave number 11 are read.
The analogue outputs begin at offset 0x800 (hex). The length indicates the
number of channels to be read.


Query

Byte Name

Example

RTU

ASCII

Start frame

„:“

0x3A

Slave address 11

0x0B

„0B“

0x30, 0x42

Function code 3

0x03

„03“

0x30, 0x33

Start address high 8

0x08

„08“

0x30, 0x38

Start address low 0

0x00

„00“

0x30, 0x30

Count high 0

0x00

„00“

0x30, 0x30

Count low 2

0x02

„02“

0x30, 0x32

Error Check

LRC / CRC

0xC6
0xC1

„E8“

0x45, 0x38


End of frame

t1-t2-t3

CRLF

0xD, 0xA


Response

The coupler answers with byte count 4, i.e. 4 bytes of data are returned.
The request was for 2 analogue channels, and these are now distributed
over 2 words. In the analogue output process image, the first channel has
the value 0x3FFF, while the second channel has the value 0x0.

Byte Name

Example

RTU

ASCII

Start frame

„:“

0x3A

Slave address 11

0x0B

„0B“

0x30, 0x42

Function code 3

0x03

„03“

0x30, 0x31

Count byte 4

0x04

„04“

0x30, 0x30

Data 1 high byte 63

0x3F

„3F“

0x33, 0x46

Data 1 low byte 255

0xFF

„FF“

0x46, 0x46

Data 2 high byte 0

0x00

„00“

0x30, 0x30

Data 2 low byte 0

0x00

„00“

0x30, 0x30

Error Check

LRC / CRC

0xC6
0xC1

„B0“

0x42, 0x30


End of frame

t1-t2-t3

CRLF

0xD, 0xA