Appendix, Modbus interface – BECKHOFF BK7300 User Manual

Page 36

Advertising
background image

Appendix

32

BK7300

Appendix


MODBUS Interface

address

Description

0x0000
0x00FF

Process data interface
inputs

0x0800
0x08FF

Process data interface
outputs

0x1000-
0x1006

Bus coupler identification

0x100A

2 byte PLC interface

0x100B

Terminal diagnostics

0x100C

Bus coupler status

0x1010

Process image length in bits

Analogue outputs

0x1011

Process image length in bits

Analogue inputs

0x1012

Process image length in bits

Digital outputs

0x1013

Process image length in bits

Digital inputs

0x1020





Only Read

Watchdog

Current time in [ms]

1000

0x110A

2 byte PLC interface

0x110B

Terminal diagnostics

0x1120


Read/Write

Watchdog

Pre-defined time in [ms]

1000

0 watchdog deactivate; max: 0xFFFF ca. 65 sec

0x1121

Watchdog Reset Register

1

Telegram watchdog

0x1122

Type of Watchdogs

0

Write telegram watchdog (default)


Watchdog
The watchdog is active under the factory settings. After the first write telegram the watchdog timer is
initiated, and is triggered each time a write telegram is received from this device. Other devices have no
effect on the watchdog. A second approach is for the watchdog only to be re-triggered after each
telegram. To do this, write a one into register 0x1122 (default value "0").
The watchdog can be deactivated by writing a zero to offset 0x1120. The watchdog register can only be
written if the watchdog is not active. The data in this register is retained.