Application Note EL9800

4

Slave Configuration

This chapter describes how to create an EtherCAT slave configuration using TwinCAT and the
EL9800 Evaluation board.

4.1

Digital I/O Slave

The ET1100 and ET1200 provide the possibility to handle up to 32 (ET1100) digital signals without a
connected local uController (and slave software). These are called simple devices. This chapter
describes how to configure such an EtherCAT slave.
NOTE: Only the piggyback board FB1111-0142 shall be used in this configuration.

a. Power off the EL9800 Evaluation board

b. Set PDI selector to position 0

c. Power on the EL9800 Evaluation board

d. Start the TwinCAT System Manager

e. Scan the network (chapter 3.3.1)

f.

Write the Device Description for 16 Bit Digital I/O to the EEPROM (Figure 18: 16Bit Digital I/O
Device Description).

How to write the EEPROM is described in chapter 3.3.2).

Figure 18: 16Bit Digital I/O Device Description

g.

After writing and verification was successful close the “Advanced Settings” Dialog

h. Power off the EL9800 evaluation board

i.

Set PDI selector to position 4

j.

Power on the EL9800 evaluation board

k.

Rescan for EtherCAT slaves (right mouse click on “Device xx (EtherCAT)”-> “Scan Boxes”

l.

If a “Configuration changed” dialog is shown click “Copy all” and acknowledge this dialog with
“OK”.

m.

Activate “Free Run” (“Free Run” can also be activated by pressing Ctrl+F5)

n. Process data communication is now running.

Outputs can be set by right mouse click on the variable and selecting

“Online write”.