4 technical data, 1 permissible ambient and operating conditions – BECKHOFF AX5000 60 A - 170 A User Manual

Page 17

Advertising
background image

BECKHOFF

Drive Technology

4 Product description

AX5000

Version: 1.4

17

4.4

Technical data

UL-Listing!
It is essential to observe chapter 3.3 if you wish to operate an AX5000 in an

economic area that requires a UL-Listing.

4.4.1

Permissible ambient and operating conditions

Ambient / operating conditions

Permissible values

Ambient temperature during operation 0 °C up to +40 °C

Up to 55 °C with reduced power (2 % / °C)

Ambient temperature during transport -25 °C up to +70 °C

Ambient temperature during storage

-25 °C up to +55 °C

Air humidity

15 % up to 85 %, non-condensing

Pollution degree

2 according to EN 60664-1

Corrosion protection

Normally not required.

Under extreme operating conditions separate

measures must be agreed with the manufacturer.

Operating altitude

up to 1000 m above sea level without reduced power.

Between 1000 m and max. 2000 m with reduced

power 1 % per 100 m.

Installation position

vertical

Ventilation

Built-in temperature-controlled fan

Protection class

IP 20 except the terminals (IP00)

EMC

Category C3 - standard

Category C2, C1 - auxiliary filter required

Advertising