1 mains supply connection (x01) – BECKHOFF AX5000 60 A - 170 A User Manual

Page 34

Advertising
background image

5 Installation

BECKHOFF

Drive Technology

34

Version: 1.4

AX5000

5.2.1

Mains supply connection (X01)

The servo drives of the AX5000 series are equipped with a wide voltage input "

X01" and can

be connected to voltage systems three-phase 400 V

AC -10%

- 480 V

AC +10%

.

Note

Connection to the standard mains supply (TT/TN) with earthed centre is

described below. Connections to other supply systems are not permissible.

Three-phase 400

-10%

- 480

+10%

V

AC


5.2.1.1

External protection for individual devices, CE-compliant

CAUTION

Fire hazard through short circuit!
The recommended fuses are designed for line protection. The servo drives

feature integrated self-protection.

Fusing

AX5160 AX5172 AX5190 AX5191 AX5192 AX5193

AC supply

*)

80 AT 100 AT 125 AT 160 AT 200 AT

224 AT

24 V supply

4 AT

10 AT

Brake resistor

electronic

*) Application class "gG" mains fuses according to IEC 60269 or "C" type automatic

circuit breakers must be used.


5.2.1.2

External protection for individual devices, UL-compliant

CAUTION

Fire hazard through short circuit!
The recommended fuses are designed for line protection. The servo drives

feature integrated self-protection.

Fusing

AX5160 AX5172 AX5190 AX5191 AX5192 AX5193

AC supply (max.)

*)

24 V supply (max.)

4 AT

10 AT

Brake resistor

electronic

*) Mains fuses according to type “RK5” min. 480 V must be used.