7 Project planning – important information

AX5000

Version: 1.4

39

7.3

EMC, earthing, screen connection and potential

The AX5000 corresponds to EMC category "C3" (industrial sector) in terms of conducted

interference emissions. If you wish to use components which comply with a higher category

you can limit the AX5000 conducted interference emissions with the aid of additional filters

to such a degree that this complies with the EMC category "C2" (residential and industrial

environment) or "C1" (residential environments).

Ensure that there is adequate earthing (large-area low-impedance connection) of all relevant

components (incl. control cabinet). The AX5000 incl. periphery, control cabinet, machine bed

and motors must be at the same potential, as the AX5000 control quality will suffer under

differing potentials and operational malfunction may result. Using the screen connection for

potential equalisation is not permitted. If you are unable to provide a uniform reference

potential you need to lay potential equalisation cables of adequate dimensions.

Smooth operation is only guaranteed by faultless screen connections of the cables. The

screens must be applied generously at both ends and must on no account be disconnected.

Use Beckhoff motor and feedback cables as these are optimally adapted to the drive system

and reduce interference to a minimum. Ensure that the connectors and cables are properly

connected.

7.4

Control cabinet

The dimensions of the control cabinet must be sufficient to accommodate all components

with the specified distances. Remember that high temperatures may necessitate forced

cooling. Position the control cabinet as close as possible to the machine so that the motor

cables can be as short as possible.

In addition, the control cabinet should have an earthed metal rear panel to which the

AX5000 incl. periphery are attached so that safe earthing can be guaranteed. If you are

unable to guarantee these conditions you need to earth the AX5000 and the relevant

components using an approved cable of adequate size.