Delta DVP-ES2 User Manual

Page 179

Advertising
background image

3 . I n s t r u c t i o n S e t

3 - 6 3

API Mnemonic Operands

Function

12

D MOV P

Move

Controllers

ES2/EX2 SS2

SA2

SE

SX2

Bit Devices

Word devices

Program Steps

Type

OP

X Y

M S K H KnX KnY KnM KnS T C D E F

S

* *

*

*

*

*

*

*

*

*

*

D

*

*

*

*

*

*

*

*

MOV, MOVP: 5 steps

DMOV, DMOVP: 9 steps

PULSE 16-bit 32-bit

ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2 ES2/EX2 SS2

SA2

SE

SX2

Operands:

S: Source of data D: Destination of data

Explanations:

1.

When this instruction is executed, the content of S will be moved directly to D. When this

instruction is not executed, the content of D remains unchanged

2. If

operand

S and D use index register F, only 16-bit instruction is applicable

Program example:

1.

MOV will move a 16-bit value from the source location to the destination.

a) When X0 = OFF, the content of D0 remains unchanged. If X0 = ON, the data in K10 is

moved to D0.

b) When X1 = OFF, the content of D10 remains unchanged. If X1 = ON, the data of T0 is

moved to D10 data register.

2.

DMOV will move a 32-bit value from the source location to the destination.

a) When X2 = OFF, the content of (D31, D30) and (D41, D40) remain unchanged.

b) When X2 = ON, the data of (D21, D20) is moved to (D31, D30) data register. Meanwhile, the

data of C235 is moved to (D41, D40) data register.

X0

X1

X2

MOV

K10

D0

MOV

T0

D10

DMOV

D20

D30

DMOV

C235

D40

Advertising