3 . I n s t r u c t i o n S e t

3 - 2 0 5

Receiving data: (External equipment -> PLC)

D120L

D122L

D123L

D124L

D125L

D126L

D121L

Registers for received data,
starting from the lower 8 bits
of D120

length = 7

STX

ETX1

ETX2

3.

The STX and ETX of external equipments will be received by PLC in data receiving process,

therefore, care should be taken on the setting of operand n (Length of data to be received).

16-bit mode:

1.

STX (Start of Text) and ETX (End of text) are set up by M1126 and M1130 together with

D1124~D1126. When PLC executed RS instruction, STX and ETX will be sent out

automatically.

2.

When M1161 = OFF, the 16-bit mode is selected, i.e. both high byte and low byte of the 16-bit

data will be received and transmitted.

M1001

M1161

D100

D120

K4

K7

RS

X0

Sending data: (PLC -> external equipment)

STX

D100L

D100H

D101L

D101H

ETX1

ETX2

Source data register, starting
from the lower 8 bits of D100

length = 4

Receiving data: (External equipment -> PLC)

D120L

D120H

D121L

D121H

D122L

D122H

D123L

ETX1

ETX2

Registers for received data,
starting from the lower 8 bits
of D120

STX

3.

The STX and ETX of external equipments will be received by PLC in data receiving process,

therefore, care should be taken on the setting of operand n (Length of data to be received)