4.5.3 Command Code: 03, Read Content of Register (T, C, D)

Example: Read coils T20~T27 from Slave ID#01

PC→PLC “: 01 03 06 14 00 08 DA CR LF”

Sent message:

Field Name

ASCII

STX :

Slave Address

01

Command code

03

Starting Address Hi

06

Starting Address Lo

14

Number of Points Hi

00

Number of Points Lo

08

Error Check (LRC)

DA

END 1

0D (Hex)

END 0

0A (Hex)

PLC→PC

“:01 03 10 00 01 00 02 00 03 00 04 00 05 00 06 00 07 00 08 B8 CR LF”

Feedback message:

Field Name

ASCII

STX :

Slave Address

01

Command code

03

Bytes Count

10

Data Hi (T20)

00

Data Lo (T20)

01

Data Hi (T21)

00

Data Lo (T21)

02

Data Hi (T22)

00

Data Lo (T22)

03

Data Hi (T23)

00

Data Lo (T23)

04

Data Hi (T24)

00

Data Lo (T24)

05

Data Hi (T25)

00

Data Lo (T25)

06