Delta DVP-ES2 User Manual

Page 404

Advertising
background image

D V P - E S 2 / E X 2 / S S 2 / S A2 / S X 2 / S E O p e r a t i o n M a n u a l - P r o g r a m m i n g

3-288

M1002

MOV

H86

D1120

SET

M1120

MOV

K100

D1129

RST

M1127

M1127

X0

RSTEF

K1

K0

SET

M1122

M1129

X0

Processing received data

Receiving completed

Communication instruction setting:
Device address: 1 K0:

Reserved

Set up communication protocol as
9600, 7, E, 1

Retain communication protocol

Set up communication time-out: 100ms

Sending request

Reset M1127.

PLC VFD, PLC sends: “:01 06 2002 0002 D5

VFD PLC, PLC sends: “:01 06 2002 0002 D5

Data to be sent (sending messages):

Data

Descriptions

‘0’

30 H

ADR 1

‘1’

31 H

ADR 0

AC drive address : ADR (1,0)

‘0’

30 H

CMD 1

‘6’

36 H

CMD 0

Command code: CMD (1,0)

‘2’ 32

H

‘0’ 30

H

‘0’ 30

H

‘2’ 32

H

Data address

‘0’ 30

H

‘0’ 30

H

‘0’ 30

H

‘2’ 32

H

Data contents

‘D’

44 H

LRC CHK 1

‘5’

35 H

LRC CHK 0

Error checksum: LRC CHK (0,1)