2.8 M

Relay

The types and functions of special auxiliary relays (special M) are listed in the table below. Care

should be taken that some devices of the same No. may bear different meanings in different series

MPUs. Special M and special D marked with “*” will be further illustrated in 2.13. Columns marked

with “R” refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains

unchanged and “#” refers to that system will set it up according to the status of the PLC.

Special

M

Function

ES2
EX2

SS2 SA2 SX2

OFF

Ø

ON

STOP

Ø

RUN

RUN

Ø

STOP

Attrib.

Latch

Default

-ed

M1000*

OFF

ON

OFF R NO

OFF

○

○

○

○

Monitor normally open contact

M1001*

ON

OFF

ON R NO

ON

○

○

○

○

Monitor normally closed contact

Enable single positive pulse at the

moment when RUN is activate (Normally

OFF)

M1002*

OFF

ON

OFF R NO

OFF

○

○

○

○

Enable single negative pulse at the

moment when RUN is activate (Normally

ON)

M1003*

ON

OFF

ON R NO

ON

○

○

○

○

M1004* ON when syntax errors occur

OFF

OFF

- R

NO

OFF

○

○

○

○

M1008*

OFF

OFF

- R

NO

OFF

○

○

○

○

Watchdog timer (ON: PLC WDT time out)

Indicate LV signal due to 24VDC
insufficiency

M1009

OFF

- - R

NO

OFF

○

○

○

○

M1011* 10ms clock pulse, 5ms ON/5ms OFF

OFF

- - R

NO

OFF

○

○

○

○

100ms clock pulse, 50ms ON / 50ms
OFF

M1012*

OFF

- - R

NO

OFF

○

○

○

○

M1013* 1s clock pulse, 0.5s ON / 0.5s OFF

OFF

- - R

NO

OFF

○

○

○

○

M1014* 1 min clock pulse, 30s ON / 30s OFF

OFF

- - R

NO

OFF

○

○

○

○

M1015* Enable high-speed timer

OFF

- -

R/W

NO

OFF

○

○

○

○

M1016*

OFF

- -

R/W

NO

OFF

○

○

○

○

Indicate Year display mode of RTC.

M1017*

OFF

- -

R/W

NO

OFF

±30 seconds correction on real time clock

○

○

○

○

M1018

Flag for Radian/Degree, ON for degree

OFF

- -

R/W

NO

OFF

○

○

○

○

2 - 1 7