LR, LRV, LLR and LR-S USER INSTRUCTIONS ENGLISH 71569088 08-10

Page 15 of 48

flowserve.com

Never use the pump as a support for

piping.

Maximum forces and moments allowed on the pump
flanges vary with the pump size and type. To minimize
these forces and moments that may, if excessive,
cause misalignment, hot bearings, worn couplings,
vibration and the possible failure of the pump casing,
the following points should be strictly followed:

Prevent excessive external pipe load

Never draw piping into place by applying force to
pump flange connections

Do not mount expansion joints so that their force,
due to internal pressure, acts on the pump flange


The table in 4.6.3 summarizes the maximum forces
and moments allowed on horizontal shaft pump
casings. Refer to Flowserve when the pump shaft is
vertical.

Ensure piping and fittings are flushed

before use.

Ensure piping for hazardous liquids is arranged

to allow pump flushing before removal of the pump.


4.6.2 Suction piping
a) The inlet pipe should be one or two sizes larger

than the pump inlet bore and pipe bends should
be as large a radius as possible.

b) Pipework reducers should be conical and have a

maximum total angle of divergence of 15 degrees.

c) On suction lift the piping should be inclined up

towards the pump inlet with eccentric reducers
incorporated to prevent air locks.

d) On positive suction, the inlet piping must have a

constant fall towards the pump.

e) Flow should enter the pump suction with uniform

flow, to minimize noise and wear. This is
particularly important on large or high-speed
pumps which should have a minimum of five
diameters of straight pipe on the pump suction
between the elbow and inlet flange. See section
10.3, Reference 1, for more detail.

f) Inlet strainers, when used, should have a net `free

area' of at least three times the inlet pipe area.

g) Do not install elbows at an angle other than

perpendicular to the shaft axis. Elbows parallel
to the shaft axis will cause uneven flow.

h) Except in unusual circumstances strainers are

not recommended in inlet piping. If considerable
foreign matter is expected a screen installed at
the entrance to the wet well is preferable.

i)

Fitting an isolation valve will allow easier
maintenance.

j)

Never throttle pump on suction side and never
place a valve directly on the pump inlet nozzle.


Typical design – flooded suction

Note:
Ideally reducers should be limited to one pipe diameter change,
ie 150 mm (6 in.) to 200 mm (8 in.). Must have a maximum total
angle of divergence of 15 degrees.

Typical design – suction lift

Notes:
1. S = Minimum submergence >3E.
2. Ideally reducers to be limited to one pipe diameter change,

ie 150 mm (6 in.) to 200 mm (8 in.). Must have a maximum
total angle of

divergence of 15 degrees.


4.6.3 Maximum forces and moments allowed on
the pump suction and discharge flanges of
horizontal shaft pumps

Suction

Discharge

Pump

axis

See table overleaf.

Non
return
valve

Concentric
conical
reducer

Eccentric
conical
reducer

>5D

Discharge
isolating
valve

Suction
isolating
valve

Slope up from
pump suction

Discharge
isolating
valve

Non
return
valve

Concentric
conical
reducer

Eccentric
conical
reducer

>5D

Long
radius
bend

Slope down
from pump
suction