Flowserve FRBHJC User Manual

Page 28

Advertising
background image

FRBHJC USER INSTRUCTIONS ENGLISH 71569179 11-04


Page 28 of 42

®


b) Check for any leaks from gaskets and seals. The

correct functioning of the shaft seal must be
checked regularly.

c) Check bearing lubricant level, and if the hours run

show a lubricant change is required.

d) Check that the duty condition is in the safe

operating range for the pump.

e) Check vibration, noise level and surface

temperature at the bearings to confirm satisfactory
operation.

f) Check dirt and dust is removed from areas around

close clearances, bearing housings and motors.

g) Check coupling alignment and re-align if

necessary.


Our specialist service personnel can help with
preventative maintenance records and provide
condition monitoring for temperature and vibration to
identify the onset of potential problems.

If any problems are found the following sequence of
actions should take place:
a) Refer to section 7, Faults; causes and remedies,

for fault diagnosis.

b) Ensure equipment complies with the

recommendations in this manual.

c) Contact Flowserve if the problem persists.

6.2.1 Routine inspection (daily/weekly)

The following checks should be made

and the appropriate action taken to remedy any
deviations:
a) Check operating behaviour. Ensure noise,

vibration and bearing temperatures are normal.

b) Check that there are no abnormal fluid or lubricant

leaks (static and dynamic seals) and that any
sealant systems (if fitted) are full and operating
normally.

c) Check that shaft seal leaks are within acceptable

limits.

d) Check the level and condition of oil lubricant. On

grease lubricated pumps, check running hours
since last recharge of grease or complete grease
change.

e) Check any auxiliary supplies eg heating/cooling (if

fitted) are functioning correctly.

&

Refer to the manuals of any associated

equipment for routine checks needed.

6.2.2 Periodic inspection (six monthly)

a)

Check foundation bolts for security

of attachment and corrosion.

b) Check pump running records for hourly usage to

determine if bearing lubricant requires changing.

c) The coupling should be checked for correct

alignment and worn driving elements.

&

Refer to the manuals of any associated

equipment for periodic checks needed.

6.2 3 Re-lubrication
Lubricant and bearing temperature analysis can be
useful in optimizing lubricant change intervals. In
general however, the following is recommended.

6.2.3.1 Grease lubrication

See section 5.2.2 for grease

recommendations.

Regrease - via grease nipples every 2 000 hours or
sooner depending on the severity of the application.

It is important not to under or over grease the bearings
as this will lead to over heating and premature failure.

a) Grease lubricated bearing housings have grease

nipples fitted in the bearing covers.

b) Move the axial seal ring back so the gap between

the pump shaft and bearing cover can be seen.

c) Connect grease gun to the nipple.
d) Press grease into the bearing housing until the first

signs of it appear in the gap between the housing
and shaft, then stop greasing.

e) V-rings should be seated at the proper distance

from the sealing surface to avoid overheating.

f) The maximum allowable operating temperatures for

anti friction bearings will vary from unit to unit,
depending on ambient and fluid temperature. The
rise above ambient should not normally exceed 55

°

C (131

°

F) or a combined maximum of 95

°

C (204

°

F).

g) A continuously rising temperature or an abrupt

temperature rise indicates a problem. If these
symptoms occur, stop the pump immediately and
investigate the cause.

TIME

TEMPERATURE

Grease change - every 4 000 hours or sooner
depending on the severity of the application.

Advertising