Flowserve 1400 Valtek Logix User Manual

Page 6

Advertising
background image

46-6

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

16. Feed the driver module wires into the main chamber

of the housing and connect them to collector board.

17. Verify that the three O-rings are in the counter-bores

on the machined platform where the spool valve
block is to be placed (Figure 19)

18. Carefully slide the block over the spool, using the

machined surface of the housing base as a register
(Figure 5). Slide the block toward the driver module
until the two retaining holes line up with the threaded
holes in the base.

19. Install two spool-valve screws and tighten securely

with a phillips screwdriver.

20. Insert the orifice into the threaded hole in the driver

module assembly. Tighten with a

1

/

4

-inch open-end

wrench (Figure 4). Attach the flexible tubing from the
interface plate to this fitting.

21. Set the minimum pressure as described on page 10.

22. Thread driver module cover into driver module bore

in the main housing.

Spool Valve Cover

The spool valve cover incorporates a coalescing filter
element in a two-piece cover. This protects the spool
valve chamber from moisture and provides a low back
pressure vent for exhaust air from the spool valve.

Replacing Filter in Spool Valve Cover

1. Make sure valve is bypassed or in a safe condition.

2. Disconnect the power and air supply to the unit.

3. Remove the spool cover by removing the screw and

sliding the cover assembly backward until the tab is
clear of the slot. The sheet metal cover may be
removed and cleaned with a brush or by blowing out
with compressed air (Figure 7).

4. Remove the O-ring from around hydrophobic filter

element and set aside (Figure 6).

5. Remove the molded filter element by pulling it

straight out of chamber cover vent piece.

6. Install O-ring into base of chamber cover vent piece

as shown in Figure 6.

7. Place new molded filter element into the chamber

cover vent piece. This element provides part of the
track to secure the O-ring installed in the last step.

8. Place spool valve shroud onto spool valve cover.

9. Place the spool valve cover assembly in place by

setting it on the ramp and sliding it until the tab seats
in the slot (Figure 7) and secure with No. 8-32 screw.

Figure 4: Driver Module Orifice

Orifice

Driver
Module
Cover

Figure 5: Spool and Block

Housing

Nylon Gaskets

Driver to
Housing Screws

Spool

Spool
Valve
Screws

Spool
Valve
Block

Figure 6: Spool Valve Cover Assembly

O-ring

Hydrophobic
Filter

Spool
Valve
Cover

Spool
Valve
Shroud

Advertising