Flowserve 520MD Digital Positioner User Manual

Page 4

Advertising
background image

4

®

User Instructions Logix 520MD - LGENIM0520-01 09/09

4 SPECiFiCATiOnS

Table 1: input Signal

Input Signal Range

4 - 20 mA (HART)

Compliance Voltage

10 VDC

Voltage Supply (maximum)

30 VDC

Minimum Required Operating

Current

3,6 mA without AO

3,83 mA with AO

Table 2: Stroke Output

Feedback Shaft Rotation

Min. 15°, max 90°

40° recommended for linear

applications

Table 3: Air Supply

Air Supply Quality

Free from moisture, oil and dust

per IEC 770 and ISA-7.0.01

Input Pressure Range

1,5 to 6,0 bar (22 to 87 psi)

Air Consumption (steady state)

0,08 Nm³/h @ 1,5 bar

(0,047 SCFM @ 22 psi)

0,12 Nm³/h @ 6,0 bar

(0,071 SCFM @ 87 psi)

Table 4: Output Signal

Output Pressure Range

0 to 100% of air supply pressure

Output Flow Capacity

2,4 Nm³/h @ 1,5 bar

(1,41 SCFM @ 22 psi)

7,0 Nm³/h @ 6,0 bar

(4,12 SCFM @ 87 psi)

Table 5: Shipping Weights

Base Positioner without

Accessories

1,2 kg (2,65 lbs)

Table 7: Environmental Conditions

Operating Temperature

Standard

-20 °C to +80 °C

(-4 °F to +178 °F)

Operating Temperature

Low

-40 °C to +80 °C

(-40 °F to +178 °F)

Transport and Storage

Temperature

-40 °C to +80 °C

(-40 °F to +178 °F)

Operating Humidity

0 to 100% non-condensing

Table 6: Performance Characteristics (typical)

Linearity

< +/- 1,0%

Resolution

< 0,1%

Repeatability

< 0,2%

Deadband

< 0,2%

Table 9: Limit Switches (optional)

Type

P&F SJ2-S1n

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-25 °C to 100 °C (-13 °F to 212 °F)

Type

P&F SJ2-Sn

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-40 °C to 100 °C (-40 °F to 212 °F)

Type

P&F SJ2-n

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-25 °C to 100 °C (-13 °F to 212 °F)

3 LOgix 520MD OVERViEW
The Logix 520MD is a two-wire, 4-20 mA input digital valve

positioner with HART communication. The Logix 520MD

positioner controls single-acting actuators with linear

and rotary mountings. The Logix 520MD is completely

powered by the 4-20 mA input signal. The minimum input

signal required to function is 3,6 mA.

Since the positioner is insensitive to supply pressure

changes and can handle supply pressures from 1,5 to 6 barg

(22 to 87 psig), a supply regulator is usually not required;

however, in applications where the supply pressure is

higher than the maximum actuator pressure rating a supply

regulator is required to lower the pressure to the actuator’s

maximum rating (not to be confused with operating range).

A coalescing air filter is recommended for all applications

Table 8: Hazardous Area Specifications

ATEX

II 1 G Ex ia IIC T5 - T6

II 3 G Ex ic IIC T5 - T6

FM

Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C

Class I Zone = Group IIC T4 Ta = 85°C

Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C

CSA

Class I Division 1, Groups A,B,C,D

Class I Division 2, Groups A,B,C,D