User Instructions Logix 520MD - LGENIM0520-01 09/09

Ensure proper wiring and shielding techniques of the

control lines, and route control lines away from elec-

tromagnetic sources that may cause unwanted noise.

An electromagnetic line filter can be used to further

eliminate noise (FLOWSERVE Part Number 10156843).

In the event of a severe electrostatic discharge near

the positioner, the device should be inspected to

ensure correct operability. It may be necessary to

recalibrate the Logix 520MD positioner to restore

operation.

9 STARTUP
9.1 Logix 520MD Local interface
The Logix 520MD local user interface allows the user

to configure the basic operation of the positioner, tune

the response, and calibrate the positioner without

additional tools or configurators. The local interface

consists of a Quick-Cal™ button for automatic zero and

span setting, along with two jog buttons for spanning

valve/actuators with no fixed internal stop in the open

position. There is also a switch block containing eight

switches. Six of the switches are for basic configuration

settings, two are for calibration options. There is also

a rotary selector switch for adjusting the positioner

gain settings. For indication of operational status or

alarm conditions there are three LEDs on the local user

interface.

9.2 initial DiP Switch Setting
Before placing the unit in service, set the DIP switches in

the “Configuration” and “Cal” boxes to the desired control

options.

nOTE: The switch settings in the Configuration box are

activated only by pressing the Quick-Cal button or by

utilizing the stroke calibration features provided by a

handheld or by Flowserve PC software.

9.2 Operation of Configuration DiP Switches Setup
The first six DIP switches are for basic configuration
1. Air Action – Must be set to match the configuration of

the valve/actuator mechanical configuration.

ATO (air-to-open) – Select ATO if increasing output pres-

sure from the positioner is tubed so it will cause the valve

to open.

ATC (air-to-close) – Select ATC if increasing output pres-

sure from the positioner is tubed so it will cause the valve

to close.

2. Signal at Closed – Normally this will be set to 4 mA for

an air-to-open actuator, and 20 mA for an air-to-close

actuator configuration.

Selecting 4 mA will make the valve fully closed when the

signal is 4 mA and fully open when the signal is 20 mA.

Selecting 20 mA will make the valve fully closed when the

signal is 20 mA and fully open when the signal is 4 mA.

Figure 4: Logix 520MD Local interface

4-20 mA Input

4-20,mA Feedback

(Optional)

Quick-Cal Button

Gain Selector

Jog Calibrate

Buttons

LED Status

Lights

Configuration Switches