Flowserve APEX A9000 Accord User Manual

Page 25

Advertising
background image

25






The Status Menu is used to select whether or not the positioner is in service.

The menu contents are shown in the figures on the right and the various
texts are described below:

o o service

Not in service.

Flashing indicator in upper left-hand corner of display.

in service

Positioner in service.

Critical parameters cannot be changed.







The Setup Menu is used for various settings.

The menu contents are shown in the chart on the next page and the various texts are described below:

Actuator

Type of actuator

Size of actuator

Time out

Rotating

Rotating actuator.

Small

10 s

Linear

Linear actuator.

Medium

25 s

Large

60 s

Extra Large

180 s

Lever

Only for linear actuator.

Lever stroke Stroke length to achieve correct display.

Level cal

Calibration of positions to achieve correct display.

Direction

Direct

Direct function (signal increase opens). Indicator/spindle rotates counter- clockwise.

Reverse

Reverse function.

Character

Curves that show position as a function of input signal.
















FULL MENU
SETUP

SIGNAL

R

OT

AT

ION

Q

O

Sqr

Lin

Eq%

Linear
Equal %
Quick Open
Square Root
Custom
Create Own Curve

Custom Characterization # of points (Specify # of pts, 3,5,9,17 or 33)
Custom Curve: Enter values on X and Y axis.
Current Range: 0%=4mA

, 100%= 20mA

Possibility of selecting which input signals correspond to 0% and 100%
movement respectively. Examples of settings: 4mA = 0%, 12mA =
100%, 12mA = 0%, 20mA = 100%







See Diagram

FULL MENU