Flowserve APEX A9000 Accord User Manual

Page 27

Advertising
background image

27



Leakage

Air leakage in actuator/tubing can be compensated by settings.

Undo You can read last 20 changes.
P,I,D and K,Ti,Td parameters

If one of the gains is changed, the corresponding value in the other gain set is changed accordingly.

Spring adjust

The spring adjust function compensates the airflow linearly with the actuator C+ chamber volume (for a constant position
error), so that low volumes get less flow. This is needed for linear single-acting actuators, where a low C+ volume means
that the actuator spring is extended, its force is reduced, and less flow is needed for stable position change.

Fiction
High or Low: Select High for high friction valve actuator assemblies such as plug valves








Deviation

Alarm generated when deviation occurs

On/Off

Alarm on/off.

Distance

Allowed distance before alarm is generated.

Time

Total deviation time before alarm is generated.

Alarm out

Select ON/OFF offers output on terminals.

Valve act

Behaviour of valve when alarm is generated.

Limit 1

Alarm above/below a certain level.

On/Off

Alarm on/off.

Minipos

Setting of desired min. position

Maxpos

Setting of desired max.position See Diagram Below!

Hysteresis

Desired hysteresis.

Alarm on

Select ON/OFF offers output on terminals.

Valve act

Behaviour of valve when alarm is generated
















Full Menu
Alarms