TRVL range

Setting end positions

0%=0.0%

Select Out of Service.

Set percentage value for desired end posi- tion (e.g. 3%).

Set 0%

Select In Service.

Connect calibrator. Move forward to desired end position (0%) and press OK.

100%=100.0%

Select Out of Service.

Set percentage value for desired end posi tion (e.g. 97%).

Set 100%

Select In Service.

Connect calibrator. Move forward to desired end position (100%) and press OK.

Trvl ctrl

Behavior at set end position

Set low

Choose between Free (go to mechanical stop), Limit (stop at set end position), and Cut off (go directly to

mechanical stop at set end position).

Set high

Similar to Set low.

Values

Select position for Cut off and Limit at the respective end positions.

Passcodes

Setting passcodes for various functions

Full menu

Passcode for access to full menu.

Write prot

Passcode for removing write protect.

Expert

Passcode for access to Expert menu (TUNING).

Fact set

Passcode to return to default values applicable when positioner was delivered.

Numbers between 0000 and 9999 can be used.

Appearance

On display

Language

Select menu language.

Units

Select units.

Def. Display

Select value(s) to be displayed during service.

The display reverts to this value 10 minutes after any change is made.

Start menu

Start in Basic menu or

Full menu.

Start Logo

Shows Flowserve Logo

Orient

Orientation of text on display.

Devicedata

HW rev

SW rev

General Parameters

Capability

HART

Menu with HART parameters. Only amendable

with HART communicator. It is possible to read from display.



The menu contents are shown in the chart on the next page and the various texts are described below:

Close time

Minimum time (Min 0.005) from fully open to closed.

Open time

Minimum time (Min 0.05) from closed to fully open.

Deadband

Setting deadband. Min. 0.2%.

Expert

Advanced settings.

Control

See explanations below.

Togglestep

Test tool for checking functions. Overlays a square wave on the

set value.

Self test

Internal test of processor, potentiometer, etc.

TUNING