2 di_position_chan, 3 di_actuator_faults_1_chan – Flowserve Limitorque MX DeviceNet Field Unit User Manual

Page 21

Advertising
background image

21

Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05

flowserve.com

4.2.1 DI_Position_and_Bus_Mode_Chan

Table 4.12

Value

Definition

0x21

Remote + Opened

0x22

Remote + Closed

0x24

Remote + Opening

0x28

Remote + Closing

0x30

Remote + Stop

0x41

Local + Opened

0x42

Local + Closed

0x44

Local + Opening

0x48

Local + Closing

0x50

Local + Stop

0x81

Stop + Opened

0x82

Stop + Closed

0x84

Stop + Opening

0x88

Stop + Closing

0x90

Stop + Stop

4.2.2 DI_Position_Chan

Table 4.13

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Reserved

Reserved

Stop

Closing

Opening

Closed

Opened

Table 4.14 – Possible values of DI_Position_Chan

Value

Definition

0x01

Opened

0x02

Closed

0x04

Opening

0x08

Closing

0x10

Stop

4.2.3 DI_Actuator_Faults_1_Chan

Table 4.15

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Reserved

Motor Over

Temp

Phase Error Over Torque Manual

Moved

Valve

Jammed

Monitor

Relay

Advertising