Table 4.16 – Possible values of DI_Actuator_Faults_1_Chan

Value

Definition

0x01

Monitor Relay

0x02

Valve Jammed

0x04

Manual Moved

0x08

Over Torque

0x10

Phase Error

0x20

Motor Over Temperature

0x03

Monitor Relay + Valve Jammed

0x05

Monitor Relay + Manual Moved

0x09

Monitor Relay + Over Torque

0x11

Monitor Relay + Phase Error

0x21

Monitor Relay + Motor Over

Temperature

0x07

Monitor Relay + Valve Jammed +

Manual Moved

0x13

Monitor Relay + Valve Jammed +

Phase Error

0x23

Monitor Relay + Valve Jammed

Motor Over Temperature

4.2.4 DI_Actuator_Faults_2_Chan

Table 4.17

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Reserved

Close

Torque

Switch Fault

Open Torque

Switch Fault

Manual

Moved

Valve

Jammed

Phase Error Thermal

Overload

Table 4.18 – Possible values of DI_Actuator_Faults_2_Chan

Value

Definition

0x01

Thermal Overload

0x02

Phase Error

0x04

Valve Jammed

0x08

Manual Moved

0x10

Open Torque Switch Fault

0x20

Close Torque Switch Fault

0x03

Thermal Overload + Phase Error

0x05

Thermal Overload + Valve Jammed

0x09

Thermal Overload + Manual Moved

0x18

Manual Moved + Open Torque Switch Fault

0x28

Manual Moved + Close Torque Switch Fault

4.2.5 DI_Actuator_Alarms_Chan

Table 4.19

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Reserved

Move Test

Active*

Not in

Remote

Close Inhibit

Active

Open Inhibit

Active

Remote ESD

Active

Local ESD

Active

* Available with Revision 1 to DeviceNet board.