3 initial actuator preparation, 1 mounting base, 2 stem acceptance – Flowserve L120 Series Limitorque Actuation Systems User Manual

Page 10

Advertising
background image

Limitorque Actuation Systems L120 Series FCD LMENIM1201-04-AQ – 05/15

10

• Carefully check for correct motor rotation direction. If the motor is driving the valve in the wrong

direction, interchange any two leads on three-phase motors or switch the armature leads on DC and
single-phase motors.

• Use a protective stem cover. Check valve stem travel and clearance before mounting covers on rising

stem valves.

• Verify all actuator wiring is in accordance with the applicable wiring diagram, national and local codes,

and Table 4.1.

Table 4.1 – Required Rating for External Wiring

Up to:

Use wire rated at least:

40°C

60°C

60°C

75°C

4.3 Initial Actuator Preparation

Replace all molded plastic conduit and top protectors (installed for shipping purposes only) with pipe
plugs when installation wiring is complete.

4.3.1 Mounting Base

The mounting hole sizes and quantities are as detailed in Table 4.2.

Table 4.2 – Mounting Base Dimensions

Actuator Size

Mounting Holes

Tap size

Quantity

MSS

ISO

L120-10

4

3

8

-16x0.88

M10x1.5x22.4

L120-20

4

5

8

-11x1.25

M16x2x32

L120-40

4

5

8

-11x1.25

M16x2x32

4.3.2 Stem Acceptance

The maximum stem acceptance is provided in Table 4.3.

Table 4.3 – Maximum Stem Acceptance

Actuator size

Drive 2

Drive 1

Tapped

Bore

Key

inch

mm

inch

mm

inch

mm

L120-10

1.25

32

1.00

25

1/4x3/32

8x6

L120-20

2.25

57

1.875

47

1/2x3/16

14x9

L120-40

2.625

66

2.125

52

1/2x3/16

16x10