Flowserve L120 Series Limitorque Actuation Systems User Manual

Page 21

Advertising
background image

21

Limitorque Actuation Systems L120 Series FCD LMENIM1201-04-AQ – 05/15

flowserve.com

Figure 5.1 (one of two) – L120-10 through 40 typical wiring diagram

MOTOR

7

3

(7)

(7C)

(3)

(3C)

R

G

(18) (18C)

(17) (17C)

(5)

(5C)

(1)

(1C)

PB1

OPEN

PB2

STOP

PB3

CLOSE

(8) (8C)

8

1

17

LOCAL

REMOTE

O

C

O

C

O

C

C

C

C

O

O

O

T1

T2

T3

L1

L2

L3

4

18

5

(4) (4C)

TH.OL

SS

OFF

ELEC HTR

MTR HTR

JUMPER

SEE NOTE #5

18

OPEN

STOP

4

2

CLOSE

3

COMMO N

YELLOW

RED

YELLOW

BLUE

YELLOW

BROWN

ORANGE

BLUE

WHITE

YELLOW

WHITE

BROWN

YELLOW

BLACK

BLUE

BLACK

P1

P1

BROWN

RED

RED

RED

WHITE

BLUE

RED

P1

PURPLE

BLACK

BLACK

POT

(OPTIONAL)

17

16

1

BLACK

BROW

N

RED

11

12

13

GREEN

BLACK

P2

H2

H1

6

5

REMOTE IND

GRAY

PINK

GRAY

REMOTE IND

21/22

BLACK

BLACK

GND

10

GREEN/WHITE

GREEN/WHITE

GREEN/WHITE

19/20

WHITE

RED

230 V

500

H1 AND H3

TO L1

H2 AND H4

TO L2

480

460

415

380

1

A

B

E

D

E

ALTERNATE

TRANSFORMER TYPES

600

575

550

-

-

3

2

TAPS

CPT

18 V

115 V

RED

WHIT

E

BLU

FUS

E

FUSE

A

B

C

D

E

BLUE

BLUE

BLACK

WHITE

RES

RES

18 V

YEL

YEL

BLU

BYPASS CIR

IND LIGHT

OPEN LIMIT

BY-PASS CIR

IND LIGHT

CLOSE LIMIT

SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE

FULLY

OPEN

A

B

FULLY

CLOSED

SPARE

SPARE

LIMIT SWITCH CONTACT DEVELOPMENT

VALVE POSITION

ROTOR

OPEN

CLOSE

INT.1

INT.2

FUNCTION

1
2
3

4
5
6
7

8
9
10
11

12
13
14
15
16

CONT

ACT

A

B

OPENING TORQUE SWITCH INTERRUPTS

CONTROL CIRCUIT IF MECHANICAL OVERLOAD

OCCURS DURING OPENING CYCLE

CLOSING TORQUE SWITCH INTERRUPTS

CONTROL CIRCUIT IF MECHANICAL OVERLOAD

OCCURS DURING CLOSING CYCLE

18

17

5. ADD JUMPER ON LS#8 BETWEEN TERMINALS (8)

Notes

3. SEE CERTIFICATION SHEET FOR VOLTAGE SUPPLIED.

2.

1.

CLOSE CONTACT

OPEN CONTACT

TRANSFORMER UNUSED WIRES TO BE SEPARATELY

COVERED WITH INSULATING HEAT SHRINK TUBING.

4. ROTORS INT.1 & INT.2 CAN BE SET AT VALVE

POSITION FULL OPEN, FULL CLOSED OR ANY

POSITION IN BETWEEN AS INDICATED BY

POINTS A AND B.

& (8C) FOR TORQUE-SEATING VALVES.

O
C

R
G

O-OPEN CONTACT
C-CLOSE CONTACT

CPT-CONTROL POWER TRANSFORMER

+-MECHANICAL INTERLOCK

TH.OL-THERMAL OVERLOAD CONTACTS

SS-SELECTOR SWITCH

(LOCAL-OFF-REMOTE )
PB1-OPEN PUSHBUTTON

PB2-STOP PUSHBUTTON

PB3-CLOSE PUSHBUTTON

ELEC HTR-COMPARTMENT HEATER

MTR HTR-MOTOR HEATER

POT-POTENTIOMETER (OPTIONAL, SEE

CERTIFICATION SHEET IF SUPPLIED)

RES-LAMP RESISTORS˛

RED INDICATING LIGHT

GREEN INDICATING LIGHT

OPENING COIL
CLOSING COIL

Legend

Valve shown in full open position