Flowserve 3400MD Digital Positioner User Manual

Page 19

Advertising
background image

19

Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ – 5/15

flowserve.com

Code

Meaning

Error
Code

Sticker

Line

Sticker Text

YYGG

Temp. High

Warning

32

14

Positioner

temperature warning

YYGG

Temp. Low

Warning

33

YYGY

Port 1 Value Out

of Range

43

15

Pressure out of

range warning

YYGY

Port 2 Value Out

of Range

44

YYGY

Port 1 Range Too

Small

45

YYGY

Port 2 Range Too

Small

46

YYGR

Supply Pressure

High

Warning

41

16

Supply pressure

high warning* **

YYYG

Supply Pressure

Low Warning

42

17

Supply pressure low

warning* **

YYYY

Actuation Ratio

Warning

16

18

Actuation ratio

warning* **

YRGG

Spool Sticking

Warning

48

19

Pilot relay response

warning*

YRRY

Electronic

Inability to Fail

Safe

39

23

Electronic fail safe

warning

YRRR

Pneumatic

Inability to Fail

Safe

17

24

Pneumatic fail safe

warning

YRGY

Friction Low

Warning

19

20

Friction low

warning*

YRGR

Pneumatic Leak

Warning

47

21

Pneumatic leak

warning*

**

YRYG

Friction High

Warning

18

22

Friction high

warning*

RGGY

Feedback Range

Too Small

56

25

Feedback calibration

range alarm

RGGY

Position Out of

Range 0

57

RGGY

Position Out of

Range 100

58

RGGR

Inner Loop Offset

Time Out

61

26

Inner loop offset

time out

alarm

RGYG

Non Settle Time

Out

60

27

Feedback non-settle

time

out alarm

Code

Meaning

Error
Code

Sticker

Line

Sticker Text

RGYY

No Motion Time

Out

59

28

Feeback no motion

time

out alarm**

RGRR

Factory Reset

State

1

29

Factory reset state.

Recalibrate

RYYG

Supply Pressure

Low Alarm

40

30

Supply pressure low

alarm* **

RRGG

Spool Sticking

Alarm

49

31

Pilot relay response

alarm*

RRGY

Friction Low

Alarm

21

32

Friction low alarm*

RRGR

Friction High

Alarm

20

33

Friction high alarm*

RRYG

Piezo Voltage

Error

35

34

Piezo voltage

alarm***

RRYR

Hall Sensor Upper

Position

52

35

Pilot relay position

limit

alarm**

RRYR

Hall Sensor

Lower Position

53

RRRY

Shunt Voltage

Reference Error

34

36

Electronics error

alarm***

RRRY

Watch Dog Time

Out

36

RRRY

NV RAM

Checksum Error

37

RRRG

Loss of Inter PCB

Comm

38

27

Loss of board

communication***

RRRR

Position Deviation

Alarm

8

38

Position deviation

alarm*

*User Set
**Check Supply
***Circuit Board Problem; See IOM

Table 9: Status and Conditions (continued)

Advertising