15 characterization retention, 1 initiating a valve signature, 2 system preparation – Flowserve 3400MD Digital Positioner User Manual

Page 23

Advertising
background image

23

Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ – 5/15

flowserve.com

Example: Stroke length is set to four inches. If the valve is moved
from 0 percent to 100 percent, four inches will be added to the travel
accumulator. The travel accumulator units will be inches. If Stroke
length is 90 degrees for a rotary, the travel accumulator will now have
units of degree. A 0 percent to 100 percent stroke will add 90 to the
travel accumulator.

Table 11: Transducer Block Characterization Parameters

Parameter

Description

Value - Meaning

Comments

MODE_BLK

The operating mode of the transducer

block

Auto - Auto (target mode)

The transducer block must be out of service

before characterization can be edited or

changed.

OOS - Out of Service

CURVE_ SELECT

Selects the characterization curve type

when the DIP switch is set to ‘Other’.

This parameter is inactive when the DIP

switch is selected to ‘Linear’.

0 - Equal Percent

Sets the characterization to equal percent

mode.

1 - Quick Open

Sets the characterization to quick open mode.

2 - Custom

Sets the characterization to use the curve fit

parameters CURVEX and CURVEY.

USER_ INTERFACE_ ACTIVE

Software version of the physical DIP

switches. The parameters can be

changed either in the parameter or at

the device via the DIP switches.

1 - Air Action

Select 1=ATO or 0=ATC
Select 1=Linear or 0=Other
Three bits of the parameter reflect the value

selected on the Rotary Actuator Gan switch

as follows:
A=111, B=011, C=101, D=001
E=110, F=010, G=100, H=000

2 - Characterization Linear

3 - Rotary Actuator Gain

CURVEX

Numeric X value array for custom point.

(1 x 21 array points)

X-axis value for custom stroke

characterization point.

Range –10 to 110

Pair each X-value with corresponding Y-value

to define the desired point. Values must be in

ascending (or equal) order.

CURVEY

Numeric Y value array for custom point.

(1 x 21 array points)

Y-axis value for custom stroke

characterization point.

Range –10 to 110

7.15 Characterization Retention

Once a custom curve has been loaded into the Logix 3400MD digital
positioner’s memory it is retained in the EPROM until it is either edited
or replaced. Turning Custom Characterization Active on or off now
selects between a linear response (off), or the new custom curve (on).
If either of the other two factory curves is selected it will overwrite
the custom curve in RAM only. The custom user-defined curve will
automatically be activated again when the factory curve is deselected.

7.15.1 Initiating a Valve Signature

A feature of the Logix 3400MD positioner is the ability to capture and
store a valve diagnostic signature. A signature is the collected data
response of the valve to a predefined set of operating conditions.
This stored data can later be uploaded to the host system for analysis
of potential problems. By comparing a baseline signature, when
the valve is new, to subsequent signatures at later times, a rate of
change can be tracked which can help predict possible faults in the
valve before they happen. This is called ‘predictive maintenance’. It is
important to note

NOTE: Stroke length is for information only and is not used during
calibration.

that the purpose of the positioner is to act as the data acquisition
device for the signature. Analysis of the data is not done on the
device, but in the supervisory system.

NOTE: Signature data is lost if the positioner is reset or if the power
is cycled.

7.15.2 System Preparation

c

DANGER: By definition, the collection of the signature requires

the unmanaged operation of the positioner. Therefore, the process

must be in a safe operating mode where unexpected movement of
the valve will not cause a hazardous condition.

Before a valve signature can be run, the Transducer Block must
Out-of-Service (OOS).