Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ –5/15

30

Fieldbus

Block Index

Fieldbus

Variable Name

Transducer

Block

Fieldbus

Datatypes

Logix Positioner

Description

Register

Type

Fix

Pt

Rd

Variable

Name

R/W

89

ACT_MAN_ID

XDTB_

MAIN

UNSIGNED 8

N/A

U_CHAR

NO

ACTman

NRW

User Info, Actuator, Manu-

facturer

90

ACT_FAIL_

ACTION

XDTB_

MAIN

UNSIGNED 8

N/A

N/A

N/A

N/A

NRW

Reserved For Future Use

91

ACT_MODEL_

NUM

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

NRW

Reserved For Future Use

92

ACT_SN

XDTB_

MAIN

VISIBLE_

STRING

231

U_CHAR

NO

ACTsn

NRW

User Info, Actuator Serial
Number

93

ACT_TYPE

XDTB_

MAIN

UNSIGNED 8

232

U_CHAR

NO

ACTtype

NRW

User Info, Actuator, Type

94

ACT_SIZE

XDTB_

MAIN

UNSIGNED 8

233

U_CHAR

NO

ACTsize

NRW

User Info, Actuator, Size

95

ACT_AREA

XDTB_

MAIN

FLOAT

209

U_INT

/10

ACTarea

NRW

Actuator Area

96

SPRING_TYPE

XDTB_

MAIN

UNSIGNED 8

234

U_CHAR

NO

SPRINGtype

NRW

User Info, Actuator, Spring

Type: single, dual, etc.

97

PO_DATE

XDTB_

MAIN

VISIBLE_

STRING

235

STRING

NO

PO_date

NRW

User Info, Purchase Order

Date

98

INSTALL_DATE

XDTB_

MAIN

VISIBLE_

STRING

236

STRING

NO

INSTALL_date

NRW

User Info, Install Date

71

VALVE_MODEL_

NUM

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

NRW

User Info, Valve Model

Number

99

MFG_PHONE

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

NRW

User Info, Manufacturer

Phone Number

100

PUR_ORDER_

NUM

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

NRW

User Info, Purchase Order

Number

102

XD_CAL_LOC

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

SRW

User Info, Calibration Location

104

XD_CAL_WHO

XDTB_

MAIN

VISIBLE_

STRING

N/A

N/A

N/A

N/A

SRW

User Info, Calibration Done by

Devide Mode and Status Parameters

13

DIAGNOS-

TICS_LEVEL

XDTB_MD

UNSIGNED 8

258

U_CHAR

NO

LD_MD_

MODE

R

Is This an LD or an MD

Device

16

CONTROLLER_

STATE_ STATUS

XDTB_

MAIN

BIT_STRING

260

U_CHAR

NO

Mode_Status

R

Status, Alarm, Mode Flags

18

POSITIONER_

STATUS

XDTB_

MAIN

BIT_STRING

261

U_CHAR

NO

Positioner_

Status

R

Status, Alarm, Positioner

Flags

14

MECHANICAL_

STATUS

XDTB_MD

BIT_STRING

262

U_CHAR

NO

Mechanical_

Status

R

Status, Alarm, Mechanical

Flags

26

CALIBRA-

TION_STATUS

XDTB_

MAIN

BIT_STRING

263

U_CHAR

NO

Calibra-

tion_Status

R

Status, Alarm, Calibration

Flags

13

ELECTRONIC_

STATUS

XDTB_

TECH

BIT_STRING

264

U_CHAR

NO

Electronic_

Status

R

Status, Alarm, Electronic

Flags

21

PRESSURE_

STATUS

XDTB_

TECH

BIT_STRING

265

U_CHAR

NO

Pres-

sure_Status

R

Status, Alarm, Pressure

Flags

15

INNERLOOP_

STATUS

XDTB_

TECH

BIT_STRING

266

U_CHAR

NO

Inner

Loop_Status

R

Status, Alarm, Inner Loop

Flags

17

OUTERLOOP_

STATUS

XDTB_

TECH

BIT_STRING

267

U_CHAR

NO

Outer

Loop_Status

R

Status, Alarm, Outer Loop

Flags

19

CONFIGURA-

TION_STATUS

XDTB_

TECH

BIT_STRING

269

U_CHAR

NO

Configura-

tion_Status

R

Status, Alarm, Configuration

Flags

17

CONTROLLER_

STATE_MASK

XDTB_

MAIN

BIT_STRING

270

U_CHAR

NO

Mode_Mask

NRW

Status, Alarm, Mode Flags