15 troubleshooting – Flowserve 3400MD Digital Positioner User Manual

Page 51

Advertising
background image

51

Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ – 5/15

flowserve.com

Table 20: Troubleshooting

Failure

Probable Cause

Corrective Action

No LED is blinking

Voltage of supply source is not high enough

Verify that voltage source can supply at least 9 V

Current draw incorrect

Verify current draw of device (23 mA) and that of

other devices on the loop aren’t pulling too much

current

Erratic communications

Maximum cable length or cable impedance

exceeded

Check cable conduction size, length and

capacitance. Refer to Section 6.4, “Cable

Requirements”

Improper grounding

Terminate and ground segment properly.

Interference with I.S. barrier

Must use FF-compatible I.S. barrier

Host FB card not configured or connected correctly Check connections and configurations of card

Unit does not respond to Final

Value commands

Unit is in Auto mode

Put in OOS mode

Error occurred during calibration

Check blink codes on positioner and correct

calibration error. Recalibrate

Positioner tubing backwards

Re-tube the actuator

Stem position sensor mounting is off 180°

Remount position sensor

Stroke not calibrated

Perform RE-CAL

Tight shutoff is active

Verify settings using PC or handheld software

Customer characterization or soft stops active

Verify customer characterization and soft stops

Position is driven fully open or closed and will not

respond to command

Stroke not calibrated

Check DIP switch settings and calibrate

valve stroke

Inner-loop hall sensor not connected

Verify hardware connections

Wrong air action entered in software

Check ATO (Air-to-open) and ATC (Air-to-close)

settings. Recalibrate

Actuator tubing backward

Verify ATO/ATC actuator tubing

Driver module Electro-pneumatic converter

malfunctioning

Replace driver module

Control parameter inner-loop offset is too high/low

Adjust inner-loop offset and see if proper control

resumes

Sticking or hunting operation of the positioner

Contamination of the driver module

Check air supply for proper filtering and meeting

ISA specifications ISA-7.0.01. Check the spool

valve for contamination

Control tuning parameters not correct

Adjust gain settings using local gain switch

Packing friction high

Enable the stability DIP switch on the local

interface and recalibrate. If problem persists,

enable pressure control with handheld

communicator or SoftTools and recalibrate

Corroded or dirty spool valve

Disassemble and clean spool valve

* Final Value Cutoff
NOTE: Refer to blink codes for self diagnostics of other errors. See document #VLAIM0046. Refer to Logix 3400/1400 Reference Manual for Fieldbus

related troubleshooting.

15 Troubleshooting

Advertising