Wiring – Flowserve NRG 16-40 User Manual

Page 19

Advertising
background image

9

Wiring

NRG 16-40, NRG 17-40, NRG 19-40, NRG 111-40

Important Note
Note that screened multi-core twisted-pair control cable is required for the BUS line, e. g. UNITRONIC

®

BUS CAN  x  x ... mm



or RE-YCYV-fl  x  x ... mm



.

Prefabricated control cables (with connector and coupler) for connecting the equipment are available as

accessories.
The baud rate (data transfer rate) dictates the cable length between the bus nodes and the total power

consumption of the sensor dictates the conductor size.

UNITRONIC

®

is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart

. Undo screws

H and remove housing cover J. Fig. 13

. Slacken plug

O with 7 mm open-end spanner but do not remove. Fig. 14

The electrode terminal box can now be turned through +/– 180°.
3. Turn electrode terminal box into desired position (+/– 80°).
4. Tighten plug

O

with

25 Nm.

5. Set node ID (see sections

“Basic Settings” and “Factory set default node IDs”).

6. Re-attach housing cover

J and fix it by using screws H.

The baud rate is set via a code switch. Reduce baud if cable is longer than specified in the table. Make

sure that all bus nodes have the same settings.
To protect the switching contacts fuse circuit with .5 A (anti-surge fuse) or according to TRD

regulations (.0 A for 7 hrs operation).
If a max. cable length of more than 125 m (up to 1000 m) is desired, make sure to modify the

baud rate settings accordingly. Please refer to Fig. 26 on page 24 for more details.

S 8

S 9

S 10

Baud rate

Cable length

Number of pairs

and conductor size [mm

2

]

OFF

ON

OFF

250 kBit/s

125 m

 x  x 0.34

Factory setting

ON

ON

OFF

5 kBit/s

50 m

 x  x 0.5

OFF

OFF

ON

00 kBit/s

335 m

 x  x 0.75

ON

OFF

ON

50 kBit/s

500 m

on request, dependent on

bus configuration

OFF

ON

ON

0 kBit/s

000 m

ON

ON

ON

0 kBit/s

000 m

Aligning terminal box

Note

Wire the control cable according to the wiring diagram with connector and coupling.

Advertising