Commissioning, Operation, Emergency operation – Flowserve NRG 16-40 User Manual

Page 25

Advertising
background image

5

Apply power to switching controller NRS -40 or NRS -40..

Commissioning

Make sure that the level electrode NRG ..-40 is properly connected to the switching controller NRS

-40 or NRS -40. according to the wiring diagram,

Fig. 22

Wiring check

Apply mains voltage

Attention

If one level electrode fails to operate the installation can continue to operate in emergency mode under

constant supervision according to TRD 40 with

one level electrode.

. Undo screws

H

and remove housing cover

J

,

Fig. 13

. Set wire link

K

of the working electrode to the

left (electrode 1), Fig. 14

3. Set node ID of the working electrode to

“002”, Fig. 14, Fig. 24

4. Attach housing cover

J

and tighten screws

H

.

Enter beginning of emergency operation in the boiler log.

An installation operating in emergency mode has to be constantly supervised.

Immediately replace faulty level electrode.

Enter end of emergency operation in the boiler log.

Operation

Use in combination with switching controller NRS -40 or NRS -40. in pressurized hot-water plants

and steam boilers working in accordance with TRD 40, TRD 60, TRD 604, EN 95, EN 953 or

other national regulations.

Emergency Operation

Water-level limiter, water-level limiting system

Emergency operation of water-level limiting system

Note

To analyse and eliminate malfunctions use “Fault finding list for troubleshooting” on

page 6!