Basic settings, Switching controller level electrode, Fig. 23 – Flowserve NRG 16-40 User Manual

Page 23

Advertising
background image

3

Basic Settings

continued

1

2

H

1

1

2

2

3

3

1 2 3

5 6 7

4

8 910

ON

1

2

3

4

5

Fig. 23

Attention

Do

not assign the same node ID twice within the CAN bus network.

Assigning / changing node ID

If several systems of the same kind are to communicate in one CAN bus network, be sure to assign

one node ID for each individual system component (e. g. controller).
. Undo screws

H

and remove housing cover

J

.

. Change code switch

L

settings as required. For more information refer to page 4.

3. Re-attach housing cover

J

and fix it with screws

H

.

K

L

Water-level limiting system

The water-level limiting system consists of one switching controller type NRS -40 and

two level

electrodes type NRG ...-40. Before starting the system make sure to configure

one of the two level

electrodes as

level electrode 2.

Set wire link

K on circuit board to the right (electrode 2), Fig. 14

Set code switch

L according to the table "Node ID"

(example:

003*). For more information see Fig. 24 and 25 on page 4.

Factory set default node IDs

NRS 1-40

ID: 001

NRS 1-40.1 ID: 001
NRS 1-41

ID: 006

NRS 1-42

ID: 020

NRS 2-40

ID: 039

NRR 2-40

ID: 040

LRR 1-40

ID: 050

NRG 16-40 ID: 002

NRG 16-40 ID: 003
NRG 16-41.1 ID: 004

TRV 5-40

ID: 005

NRG 16-41 ID: 007

NRG 16-42 ID: 021
NRG 26-40 ID: 041

LRG 16-40

ID: 051

Switching Controller

Level Electrode

Advertising