Installation

Power Requirements

This equipment is designed for nominal 24 V dc operation (22 to 28.8 V) with the negative side
grounded, 20 amps maximum, 2 amps idle. However, neither power supply lead is actually wired to the
ground terminal.

The Centra-Page system may be used with negative ground, positive ground, or ungrounded power
sources. The card rack must be mounted in a non-hazardous area.

If installing a station and line card as an add-on, please consult the following chart to ensure proper power
will be supplied.

Power Supply Current Requirements

Mode

10 Cards

20 Cards

30 Cards

Standby

0.8 amp

1.5 amps

2.3 amps

Page (maximum load)

5.7 amps

11.4 amps

17.1 amps

Alarm (typical)

3.8 amps

7.5 amps

11.3 amps

Alarm (maximum level)

12.5 amps

25.0 amps

37.5 amps

Notes regarding power supply current requirements listed above:

1. Ratings at 27.0 V dc at the central cabinet. Add 8% for page and alarm at 28.8 V dc.

2. Full load is defined as 15-watt load on all cards with levels adjusted at factory; 2-watt alarm output.

3. Typical load is defined as 7.5-watt load (such as 16-ohm loudspeaker connected to 8-ohm output).

4. Maximum level is defined as 15-watt loads and level control adjusted for 15-watt alarm level on all

cards.

5. Ratings for alarm based on continuous tones. Pulse tone reduces current to about 60%.