Grounding Requirements

This unit must be grounded in accordance with the National Electrical Code (NEC) in the United States or
the Canadian Electrical Codes (CEC) in Canada. A #10 grounding stud has been provided at the base of
the stanchion for grounding. Connect the #10 grounding stud to a grounding electrode. A grounding
electrode rod is typically 8 feet (2.44 m) long per NEC 250, or 9.84 feet (3 m) long per CEC Rule 10.

Figure 3. Conduit/Surge Protection Locations